Colt SMOKEMASTER Fixed Curtains
Colt can provide fixed curtains that are designed either for the channelling or containment of smoke in the event of a fire, or for sealing off an area to contain a fire and to prevent it from spreading to other areas.
The curtain comprises a flexible, heat resistant fabric hung from the building structure.
The Smokemaster fixed smoke curtain has been tested to and fully meets the requirements of prEN 12101-1 (2003) and BS 7346 Part 3 (1990). It will withstand a temperature of up to 600 °C for 30 minutes and therefore achieves a D30 rating. Smokemaster is also available in a D120 version, following tests to 600 °C for 120 minutes in accordance with prEN 12101-1 (2003). Smokemaster is CE marked.
CPD seminars
| © 2009 Colt International Licensing Ltd - People feel better in Colt conditions |
| |