Colt Cyclone 50 Car Park Induction Jet Fan
Description
Colt Cyclone Car Park Induction Jet Fan – for controlling air movement in a car park or underground service area. Tested and certified to EN 12101-3.
Low profile high velocity powered car park induction ventilation unit, for directing exhaust fumes (in day to day mode) and smoke in a controlled manner towards the main extract positions of a car park or underground service area.
Incorporating a backward curved centrifugal impeller within a low profile slim-line casing manufactured from 1.5mm pre-galvanised steel with an outlet diffuser enabling flush fit with the underside of the car park ceiling.
Types
- Maximum 50 N thrust: unit height of 271mm
Note there is an alternative Cyclone 100 fan available.
Max. discharge velocity
Max. air flow
Motor power (full speed)
- 1.38 kW (IP 55 protection)
Options
- Single speed DOL motor suitable for inverter speed control, IP55 protection
- Two speed tap wound motor (full and half speed), IP55 protection
Motors supplied as standard with a IP65 lockable fire rated isolator or optionally with a fitted IP55 terminal box.
Finishes
- Pre-galvanised sheet (standard)
- Polyester powder coating to RAL 7035 light grey
- Polyester powder coating to any other RAL colour
Fire performance
- F300 - continuous operation for one hour at 300ºC (Cyclone achieved 2 hours under test).
Sound emissions
CIBSE Guide Volume A: 1999, Environmental Design, sets out a recommended maximum noise level of NR55 in car parks. Colt car park systems can be designed to achieve these noise levels if required.
Compliance
The complete unit, including isolator, is rated at 300°C for 120 minutes, Class F300 to EN 12101-3 (2002). Cyclone is fully CE marked.