Coltlite - LWT32

Description

Coltlite LWT 32 natural louvred ventilator, suitable for natural day to day ventilation and smoke control. Tested to and in compliance with EN 12101-2, and CE marked. For installation in the vertical only.

Detailed Description

Thermally broken extruded aluminium outer frame, 47mm thick, with framed louvres set into thermally broken frames.

Dimensions / size range

From 250mm to 1800mm in width, and from 200mm to 3000mm in height as one module.

Frame

Thermally broken, 47mm deep. Glazing seals comprise double weather strips with a nylon lip between, and the horizontal glass edges of the louvres are enclosed with aluminium sections which have two overlapping weather seals for excellent air-tightness.

Louvres

  • 32mm overall clear toughened, float or laminated double glass (6-20-6).
  • 32mm overall insulated metal skin panel infill.

Visible width of horizontal louvre frame 44mm when looking from the outside

Blade Pitch

150- 350mm (depending on overall size of complete unit) with central pivot point. Blade frame to be a maximum of 44mm between glass surfaces.

Colours/ finishes options

  • Polyester powder paint to a RAL colour, standard 75 mu
  • Anodised, standard 20 mu

Fixing options

  • Fixing to curtain walling using 24 to 36mm thermally broken glazing frame adaptor
  • Fixing to structural opening using either through frame or strap fixings.

Controls options

  • Lever
  • Crank handle
  • 230 volt AC motor
  • 24 volt DC motor
  • Pneumatic cylinder

Frame mounted motor (hidden behind side frame profile) positioned at:

  • Top
  • Bottom

on either side frame and with a typical operation time of 15-30 seconds.

  • Optional device to reduce the speed and force of closing louvres, to reduce the risk of finger squeezing (electric versions only).

If used as a smoke ventilator, activation is either by local thermal fuse which opens the unit at a pre-selected temperature, or by responding to an external release signal.

Performance

 
Reliability RE 1000 (10,000 cycles)
Wind load class Varies with size and options, up to WL 2000
Snow  load class SL 0
High temperature class B 300
Low temperature class T(00) to T(-25)
Materials resistance to fire E (to EN 13501-1)
U value up to max 1.8 W/m²K
Aerodynamic coefficient Up to 0.56
Air permeability 5.09m³/hr/m² or 0.85m³/hr/m at 50Pa
Water tightness Watertight at static pressure of up to and including 150Pa
Sound insulation Weighted sound reduction index R’w up to 38 dB

Compliance

Tested to and in compliance with EN 12101-2 and CE marked.